Do you have any questions or need more information? Then please contact us!
Vortex flow sensor VAR TwinPipe for flow velocity measurement in traffic tunnels, mining galleries and waste disposal sites, with +/- flow direction sensing.
Sensor material: stainless steel.
Dimensions L/H/W: 500/220/320 mm
Example for common applications:
Measuring range
+/-0.4 ... +/-25 m/s
Media temperature
-40 ... +80 °C
Media
air, exhaust air (gases)
Displayed indicators
flow velocity
IP protection type
IP67 (connection housing)
Type of protection
ATEX category 3G and 3D (zone 2 and 22) (optional)
Sensor output
analog output v
flow velocity or flow rate 4-20 mA or 4-12-20 mA
relay for limit value or directional flow sensing