Measuring tube VA Di with inside diameter 24 mm.
Probe materials: stainless steel.
Working temperature range up to +100 °C.
Sensor length 150 mm. Process connection with threaded connection G 1”
Suitable for fixed measuring of actual flow rate V/t [m³/h], flow velocity v [m/s] in clean as well as condensate and particle-laden gases.
Signal evalutaion with integrated transducer UVA.
An additional isolation / supply unit is necessary for ATEX applications category 1/2G and category 1/2D (zone 0, zone 20).
Output signals:
4-20 mA (flow-proportional)quantity pulse / limit value
Configurable via RS232 interface and software UCOM.
Example for a common application:
Measuring landfill gas
Leakage measurement at large ball valves in gas pipelines
Measuring range
0.4 ... 30 m/s,
0.67 ... 50 m³/h
Pressure resistance
up to 10 bar / 1 MPa overpressure
Media temperature
-40 ... +100 °C
Media
gases
Displayed indicators
flow rate, flow velocity, quantity
IP protection type
IP65 (connection housing)
Type of protection
ATEX category 3G and 3D (zone 2 and 22) (optional)
Sensor output
analog output 4-20 mA, limit value, quantity pulse, RS232 interface